Power
• Class 1
• Primary and secondary 400 V 3Ph 50 Hz supplies into internally fitted Automatic
Transfer Switch (ATS) unit or from external ATS unit
• Isolating switch in panel face for service requirements
• Current draw between 1 to 29.1 A depending on either quiescent state or system activated state and associated fan Full Load Curren (FLC): 3 kW - 11 kW: 4.7 to 21.3 A FLC
• PLC backup battery 2 x 12 V 12.0 Ah sealed lead-acid batteries (batteries not included).
Environment
• IP rating 55 (Internal and External) fully weatherproofed
• Internal or external panel fitting option
• Humidity 10 to 90% non-condensing
• Operating temperature -5 to 40°C (internally climate controlled via cooling fan and heater)
• Can be installed up to 1,000 metres above sea level without de-rating
• Fan can be installed up to 50 metres away from the panel
• Standard Finish:
Panel: Powder Coated RAL 7035
Canopy: Powder Coated RAL 5020
Miscellaneous
Note: The below are all dependent on a variety of factors, including, but not limited to, system specification, inverter size, ATS requirements, additional NV fan control and panel location.
• Weight from 140 kg up to 210 kg
• Bottom cable entry regardless of panel location