Power
• Supply 230V ac 50/60 Hz from a 5A fused unswitched spur
• Output nominal 24 Vdc 2-Channels, max 8A for 60 seconds. Peak current
combined output can exceed 8A for a short duration
• Backup battery 2 x 12V dc 7.0Ah sealed lead-acid batteries (backup battery
included)
• Battery standby time 72 hours with maximum 40mA standby drain
on PER permanent*
• Expected battery life 3+ years @ 25°C
• Real time clock battery life is 10 years
Environment
• IP rating 30
• Humidity range 10 to 90% Non-condensing
• Storage -20 to +50°C
• Operating temperature -5 to 40°C**
Miscellaneous
• Dimensions 364.5 x 337.8 x 128.4mm
• Mass approx 13kg with batteries
• Cable entry is via 15 x 20mm end mounted cable glands and/or one rear entry
slot for concealed connection
• Internal temperature sensor installed to provide optimal battery charging
compensation as the ambient temperature changes
* Standby drain current comprises of enabled fire inputs, communication cards, and other loads connected to PER.
** Operation at elevated temperatures may reduce battery life.