Electrical Supply
Input Voltage; 230V ac, 50/60Hz (± 10%) supplied from a 5A unswitched spur
Power Consumption: 500 VA
Output Characteristics
Typical Output Voltage (Mains Power / Max Load 7.0A)
Nominal: 24.0 V
Maximum: 28.4 V at 253 V ac
Minimum: 18.2 V at 207 V ac
Typical Output Voltage (No Mains Power):
Nominal: 24.0 V
Maximum: 28.8 V
Minimum: 18.5 V
Maximum Current Output (Mains and Battery Combined)
7.0 A for up to 180 seconds
Peak current may exceed 7.0A for a short duration*
Auxiliary Outputs (VC, VO, VE): Nominal 24.0 V. 100 mA / 40 mA
Battery Backup
Battery Type: 2 x 12V dc, 12.0 Ah sealed lead-acid batteries (sold separately)
Battery Standby Time: 72 hours*
Expected battery Life: 3+ years at 25°C
Real-Time Clock Battery Life: 10 years
Environmental Conditions
Humidity: 10% to 90% non-condensing
Storage Temperature: -20°C to +50°C
Operating Temperature: -5°C to 40°C
Physical Characteristics
Cable Entries:
Up to 6 x 20mm end mounted cable glands
1 x rear entry slot for concealed installation
Dimensions (W x H x D): 310 x 380 x 130 mm
Mass Approx. 4.1 kg
Notes:
* On mains failure, the average auxiliary current must be less than 40 mA to achieve 72 hours of battery backup.
Peak current values may exceed rated limited briefly during transient demand.