发布您的产品
Auxiliary Power Supplies
Edwards

Auxiliary Power Supplies

4.6 星(最高 5 星)4.6(7 评价)

Overview:

The Auxiliary Power Supply (APS) is a UL 864, 10th-Edition-listed power supply. It is a 24-Vdc filtered-regulated and supervised unit that can easily be configured to provide additional notification appliance circuits (NACs) or auxiliary power for Mass Notification/ Emergency Communication (MNEC), as well as life safety applications. 

The APS contains the circuitry to monitor and charge internal or external batteries. Its steel enclosure has room for up to two 24 ampere-hour batteries. The APS has four Class B (convertible to two Class A) NACs. These can be activated in one or two groups from the APS’s unique dual-input circuits. The APS has a door-mounted AC power indicator LED. 

The APS also has room for and can power a number of different modules. These can be Signature AA-30 or AA-50 dual-channel audio amplifiers, SIGA-UIO modules and/or SIGA-RELs. An MN-BRKT3F can also be installed. This bracket can accommodate an MN-FNS4C2F3 or MN-FNS8C2F3 Ethernet network switch, an MN-FVPN VoIP module and an MN-COM1S Communications module. 

The APS is available in 6.5 or 10 ampere models. Each output circuit has a capacity of three amperes; total current draw cannot exceed the unit’s rating. Features:

  • Allows for reliable filtered and regulated power to be installed where needed
  • Cost-effective system expansion
  • Provides for Genesis and Enhanced Integrity notification appliance synchronization
  • Supports coded output operation
  • Self-restoring overcurrent protection
  • Multiple signal rates
  • Can be cascaded or controlled independently
  • Easy field configuration
  • On-board diagnostic LEDs identify wiring or internal faults
  • Standard EDWARDS keyed lockable steel cabinet with removable door
  • 110 and 230 Vac models available
  • Accommodates 18 to 12 AWG wire size
  • Optional tamper switch
  • Dual-battery charging rates
  • Optional earthquake hardening: OSHPD seismic pre-approval for component Importance Factor 1.5

The APS meets current UL requirements and is listed under the following standards:

  • Standard (CCN) Description
  • UL864 10th-Edition (UOXX) Fire Alarm Systems
  • UL636 (ANET, UEHX7) Holdup Alarm Units and Systems
  • UL609 (AOTX, AOTX7) Local Burglar Alarm Units and Systems
  • UL365 (APAW, APAW7) Police Station Connected Burglar Alarm Units and Systems
  • UL1076 (APOU, APOU7) Proprietary Burglar Alarm System Units
  • UL1610 (AMCX) Central Station Alarm Unit
  • ULC-S527 (UOXXC) Control Units, Fire Alarm (Canada)
  • ULC-S303 (AOTX7) Local Burglar Alarm Units and Systems (Canada)
  • C22.2 No. 205 Signaling Equipment (Canada)
规格
  • Engineering Specification:

    Supply, where needed, EDWARDS APS Series Auxiliary Power Supplies (APS) that are interconnected to and supervised by the main system. The APS shall function as a stand-alone auxiliary power supply with its own fully-supervised battery complement. The APS battery complement shall be sized to match the requirements of the main system. The APS shall be capable of supervising and charging batteries having the capacity of 65 ampere-hours for Mass Notification/Emergency Communication (MNEC), life safety and security applications. 

    <>The APS shall provide a minimum of four independent, fully supervised Class B circuits that can be field-configurable for notification appliance circuits or auxiliary 24 Vdc power circuits. APS NACs shall be convertible to a minimum of two Class A NACs. Each APS output circuit shall be rated at 3 amperes at 24 Vdc. Each output circuit shall be provided with automatically restoring overcurrent protection. The APS shall be operable from the main system NAC and/or EDWARDS Signature Series control modules. APS NACs shall be configurable for continuous, 3-3-3 temporal rate. Fault conditions on the APS shall not impede operation of main system NAC. The APS shall be provided with ground fault detection circuitry and a separate AC fail relay.

技术规格
  • 唯一参考edwards-utc-020
  • 产品系列Electronics
  • 产品组Fire Detection, Monitoring and Alarm
  • 类型对象(单个对象)
  • 发布日期2018-01-07
  • 版本号1
相关
  • 主材料金属
  • 设计国家/地区United States
  • 制造国家/地区China
分类
  • BIMobject 类别消防产品 - 消防
  • IFC 分类警报
  • ETIM 代码EC002685
  • ETIM 名称Central fire alarm system
  • UNSPSC 名称Alarm systems
  • UNSPSC 代码46171604
  • Uniclass 2015 代码Pr_75_75_30_29
  • Uniclass 2015 说明Fire alarm panels
  • CSI MasterFormat 2014 代码28 31 63
  • CSI MasterFormat 2014 标题Fire Alarm Integrated Audio Visual Evacuation Systems
  • OmniClass 编号23-29 31 13
  • OmniClass 标题Fire Alarm Control Panels
  • CSI UniFormat II 代码D40
  • CSI UniFormat II 标题FIRE PROTECTION

发售地区

North America
United States
Common.Footer.ValueProp.Image.AltText

Revit 版 Design App

只需单击一下,即可将族直接加载到您的 Revit 模型中

获取一个更轻松地访问新对象、存储 Revit 族以及与团队协作的地方。

  • 勾选标记直接与 Revit 旁边的 BIM 对象一起工作
  • 勾选标记 2GB 云存储 - 存储您的 Revit 内容
  • 勾选标记 直接从 Revit 获取内含碳 LCA (A1-A3)