The Reduced Pressure Principle Backflow Preventer shall be shall be ASSE® Listed 1013, rated to 180°F, and supplied with full port ball valves. The main body and access covers shall be bronze (ASTM B 584), the seat ring and all internal polymers shall be Noryl™ and the seat disc elastomers shall be silicone. The first and second checks shall be accessible for maintenance without removing the relief valve or the entire device from the line. If installed indoors, the installation shall be supplied with an air gap adapter. For use in non-potable applications only. The Reduced Pressure Principle Backflow Preventer shall be a ZURN WILKINS Model 975XL.
Features:
- Wye pattern design reduces installation time and costs
- A tried and true design favored by installers worldwide
- Easy access to the first check for debris removal reduces maintenance costs
- Entire unit serviceable in line