Power Conditioner
Maximum Output Current, Total - 15 Amps @ 120 Volts AC
Maximum Output Current, Per Outlet/Bank - 15 Amps @ 120 Volts AC (subject to a maximum total output current of 15 Amps for all outlets combined)
Filtration - 40 dB @ 100 kHz, 50 dB @ 300 kHz, with 50 Ohm load
Surge Protection Modes - L-G, L-N, N-G
Surge Protection Shutoff - Shuts off rear outlets if surge protection is compromised
Energy Dissipation - 2000 Joules per Mode
Clamping Voltage - 370 Volts
Clamping Time - 1 ns
Wiring Fault Detection - Shuts off rear outlets if a wiring fault is detected at the input [1]
Under-Voltage Cutoff - Shuts off rear outlets if input drops below 93 Volts
Over-Voltage Cutoff - Shuts off rear outlets if input exceeds 135 Volts
Turn-On Delay - SWITCHED ON 1: 0 seconds; SWITCHED ON 2: 0 seconds; DELAYED ON 1: 1 second; DELAYED ON 2: 2 seconds
Power
Line Power - 15 Amps @ 120 Volts AC, 60 Hz
Power Consumption - ~10 Watts typical, 30 Watts maximum (not including load)
Connectors
120V~ 15A 60Hz - (1) Attached 9.8 ft (3 m) grounded AC power cord with NEMA 5-15P plug; Line power input
SWITCHED ON 1 - (2) NEMA 5-15R AC power outlets; Switched 120 Volt AC power outlet bank; Turn-On Delay: 0 seconds
SWITCHED ON 2 - (2) NEMA 5-15R AC power outlets; Switched 120 Volt AC power outlet bank; Turn-On Delay: 0 seconds
DELAYED ON 1 - (2) NEMA 5-15R AC power outlets; Switched 120 Volt AC power outlet bank; Turn-On Delay: 1 second
DELAYED ON 2 - (2) NEMA 5-15R AC power outlets; Switched 120 Volt AC power outlet bank; Turn-On Delay: 2 seconds
PROTECTION - (1) 2-pin 3.5 mm detachable terminal block; Normally open, isolated relay; Rated 1 Amp, 30 Volts AC/DC; Provides a dry contact closure if surge protection is compromised
G - (1) 6-32 screw, chassis ground lug
ALWAYS ON (front) - (1) NEMA 5-15R AC power outlet; Unswitched 120 Volt AC power outlet
Controls & Indicators
PWR - (1) Bi-color green/amber LED, indicates line power is present and the power switch is on (green) or off (amber)
FAULT - (1) Red LED, indicates any of the following fault conditions: surge protection is compromised, line and neutral are reversed, or no ground is detected [1]
PROTECT - (1) Green LED, indicates surge protection is fully functional
SHUTDOWN - (1) Amber LED, indicates power to the rear outlets is shut off due to an over-voltage, under-voltage, line input miswire, missing ground, or compromised surge protection fault condition
Power Switch - (1) Rocker switch, "On" position initiates turn-on delay sequence to the rear panel outlets, "Off" position turns all rear outlets off immediately
THERMAL BREAKER (rear) - Disrupts power to all outlets in case of an overload condition, press to reset after overload condition is resolved
Environmental
Temperature - 32° to 113° F (0° to 45° C)
Humidity - 10% to 90% RH (non-condensing)
Heat Dissipation - 34 BTU/hr typical; 102 BTU/hr maximum
Construction
Chassis - Steel, black finish
Front Panel - Extruded aluminum, black finish, polycarbonate label overlay
Mounting - 1 RU 19-inch rack-mountable (rack ears included)
Dimensions
Height - 1.73 in (44 mm) without feet
Width - 17.32 in (440 mm); 19.00 in (483 mm) with rack ears
Depth - 10.56 in (269 mm)
Weight - 8.2 lb (3.8 kg)
Compliance
UL 1449 Type 3 Listed
1. Detects most input line wiring faults. Does not detect neutral/ground reversal. Does not discern between ground connections at the AC power line, chassis, or connected equipment (a ground connection at any point will be detected by the PC-100 as normal). The installer is responsible for proper wiring and grounding of this and all connected equipment according to applicable electrical codes, accepted guidelines, and best practices. Proper wiring and function of the AC power source should be verified prior to connecting the PC-100 or any other equipment. Use of this product does not negate the responsibilities of the installer and end-user to exercise all appropriate and required measures for safe and reliable installation and operation.