Smoke curtain Smoke PROtec
Classification: EN 12101-1, ASB 3, D120 (fail-safe)
Fire resistance time: 2 hours at 600° C (in accordance with DIN EN12101-1)
Fabric: One-sided PU-coated glass fabric, 570 g/m², color grey, Non–flammable according to DIN 4102-1, A2, smoke-proof, tested in accordance with DIN EN 1634-3.
Unwind: By force of gravity (gravity fail safe)
Windup: Via planetary geared-motor, 24 V DC, engine speed sensor, maximum torque 4 Nm, integrated into the winding shaft, including 2 m connection cable.
Installation: Ceiling, wall, vertical unwinding.
System size: System width ≤ 5960 mm (Single roller), System width ≤ 30000 mm (Multiple roller), Unwinding length ≤ 6000 mm.
Head box: Galvanized sheet steel 1.0 mm, powder-coated in RAL 7035.
End section: Sheet steel 1.0 mm powder-coated in RAL 70352 with integrated unwind weights in fabric bag.
Side guides (optional): Steel 1.5 mm powder-coated in RAL 7035