The intelliTRACE ITAS and ITLS Series is a micro-processor based Control/Monitoring and Power Management system for Ambient Sensing, Line Sensing or a combination of Line and Ambient Sensing Heat Trace Applications and is suitable for use in ordinary areas.
The base panels will handle 6 - 36 loops and may be increased up to 72 loops with the Extension Panels. Each circuit has a 40 Amperage capacity and accepts 100 to 600 VAC service. The SCR Control may be set to Automatic, which includes PID or On/Off control or to Manual, which spans a 0% to 100% control output.
The HMI is a 10” (25 cm) user friendly touch screen computer. It displays the process variable, temperature setpoint, alarm status, current load, control mode, sensor failure manual override output for any 6 loops at a time as well as the alarm status for all other loops. The standard enclosure is rated for NEMA 4 environments and an optional NEMA 4X 304 SS enclosure is available.
The ITAS / ITLS Control Panel Series provide alarms for high and low temperatures, current load, communications, sensor faults and ground fault leakage. There are several output/control behavior scenarios for the ground fault (GFEP) alarm condition. Choices include Trip and/or Latch options in which both, either or none may be enabled. Trip sets the output to zero %, while Latch requires a manual reset. Alarm events are automatically logged and stored for easy access.
Advanced standard features include a proprietary soft start function, off duty Auto Cycle maintenance program and either Modbus RTU/RS485 or Ethernet communications. Optional features include an industry leading I/O (Sensor & Output) Mapping** function, remote monitoring and wireless communications.