Power
Incoming Supply: 230 V AC, 50/60 Hz from a dedicated, fully compliant supply source.
DC Output: Nominal 24 V DC multi-channel output.
Maximum 16 A per channel.
Maximum total load across all channels shall not exceed 30 A, 60 A, or 90 A, dependent on controller model selection.
Battery Backup (Optional): Supports 2 × 12 V DC, 22.0 Ah sealed lead-acid batteries per 30 A output (batteries supplied separately).
Standby Duration: Up to 72 hours, based on a maximum standby drain of 100 mA on permanent supply (PER).
Battery Service Life: Typically 3+ years at a nominal temperature of 25°C (operation at elevated temperatures may reduce battery life).
Real-Time Clock Backup Battery: Service life approximately 10 years.
Internal Thermal Management: Integrated temperature sensor provides compensated battery charging based on ambient temperature conditions.
Environment
IP Rating: IP30 enclosure.
Humidity Range: 10–90% RH, non-condensing.
Storage Temperature: −20°C to +50°C.
Operating Temperature – Control Panel: −5°C to +40°C (excluding battery performance limitations).
Mechanical and Installation
Cable Management: Cable entry via 32 × 20 mm top-mounted cable glands for structured and compliant wiring access.
Mounting: Suitable for indoor installation in a controlled environment.
Ambient conditions must meet operational limits to maintain battery performance and expected service life.